The Schneider GV2ME06, GV2ME07, and GV2ME08C are Motor Protection Circuit Breakers (MPCB) designed to protect electric motors from damage caused by overloads, short circuits, and other faults.
Description:
Product Name: Schneider GV2ME06, GV2ME07, and GV2ME08C
Type: Motor Protection Circuit Breaker (MPCB)
Application: These breakers are used for motor protection in industrial, commercial, and residential applications. They offer overload, short-circuit, and phase failure protection to ensure the safe operation of motors.
Rated Current:
GV2ME06: 6 Amperes
GV2ME07: 7 Amperes
GV2ME08C: 8 Amperes
Poles Configuration: 3P (Three Poles)
Rated Voltage: 415V AC (standard for motor protection circuits)
Rated Frequency: 50/60 Hz
Mounting Type: DIN rail mountable for easy installation in motor control panels or distribution boards.
Breaking Capacity: 6kA at 415V AC
Key Specifications:
Rated Current:
GV2ME06: 6A
GV2ME07: 7A
GV2ME08C: 8A
Poles Configuration: 3P (Three Poles)
Rated Operational Voltage: 415V AC
Rated Insulation Voltage (Ui): 690V AC
Rated Ultimate Short-Circuit Breaking Capacity (Icu): 6kA at 415V AC
Rated Working Short-Circuit Breaking Capacity (Ics): 6kA at 415V AC
Conventional Free Air Thermal Current (Ith):
GV2ME06: 6A
GV2ME07: 7A
GV2ME08C: 8A
Temperature Range: -25°C to +60°C
Mechanical Life: 10 million operations
Electrical Life: 10,000 operations
Protection Class: IP20 (providing protection against contact with fingers or solid objects larger than 12mm)
Trip Unit: Thermal-magnetic, providing both overload and short-circuit protection.