The ILS2K851PC1A0 is an Electronic Overload Relay module from Schneider Electric's TeSys Island digital motor control and management system. It is a fully integrated, intelligent protection device designed to replace traditional thermal overload relays, offering superior accuracy, configurability, and diagnostic capabilities.
Specifications:
Parameter Specification
Product Range TeSys Island
Device Type Electronic Overload Relay (Direct Mounting)
Rated Operational Current (Iu) 85 A (Setting range: 0.4 - 1.0 x Iu, i.e., 34 A to 85 A).
Motor Power Range (Reference) ~ 40 kW / 55 HP (at 400V AC)
Protection Functions • Thermal Overload Protection (Class 10A trip curve)
• Phase Unbalance / Loss Detection
• Jam Protection (Short-circuit or locked rotor)
• Ground Fault Protection (Optional, via external sensor and module)
• Undercurrent Protection (Optional)
Current Sensing Internal Current Transformers (CTs) - Direct connection to main power (no external sensors needed for basic functions).
Rated Insulation Voltage (Ui) 690 V AC
Power Supply 24V DC (Supplied via the connected TeSys Island communication base).
Auxiliary Contacts 1 NO (Normally Open) + 1 NC (Normally Closed) fault signaling contacts (rated for control circuits).
Mounting Direct mounting onto a compatible TeSys Island contactor or disconnect block (e.g., ILS1C, ILS1D series) to form a complete motor starter.
Communication Interface Requires a TeSys Island Communication Base (e.g., ILB1BL series). Enables protocols: EtherNet/IP, Modbus TCP, PROFINET.
Local Interface (LCI) Graphical display, navigation push buttons, LED indicators for Power, Run, Fault, Communication. Allows for local parameter setting and real-time current/temperature display.
Standards & Approvals UL 508, CSA C22.2 No. 14, IEC/EN 60947-4-1, IEC/EN 60947-5-1, CE, RoHS.