The Schneider Electric TM100C40RN is a 100 A, 3-pole, Thermal-Magnetic Circuit Breaker from the Compact NSX series. It is a Fixed Version, Non-Automatic Release model, designed for disconnect and protection functions in low-voltage electrical distribution systems.
Specifications
Parameter Category Details
Manufacturer & Series Schneider Electric, Compact NSX
Complete Model Number TM100C40RN
Device Type 3-Pole, Thermal-Magnetic Circuit Breaker (Fixed Version)
Rated Current (In) 100 A (Frame size: 100A)
Rated Ultimate Breaking Capacity (Icu) 36 kA at 415V AC (IEC 60947-2)
Rated Service Breaking Capacity (Ics) 75% of Icu (Typically 27 kA at 415V AC)
Number of Poles 3
Trip Unit Type Micrologic 1.3 Electronic Trip Unit ("RN" designation)
• Protection Functions: Long-time overload protection (L) only.
• Adjustments: Long-time protection current (Ir), Long-time delay (tr).
• No Short-Circuit (I) or Ground Fault (G) settings.
Long-Time Protection (Ir) Adjustable from 0.4 to 1 x In (i.e., 40A to 100A for this 100A model)
Operating Mechanism Rotary handle for ON/OFF/reset operations. Can be padlocked in the OFF position.
Terminal Type Screw terminals suitable for both front and rear cable connections.
Connection Capacity (Rigid Cable) Up to 35 mm² (or equivalent AWG) per pole.
Mounting Fixed Mounting (Direct mounting to panel backplate using screws).
Standards & Certifications IEC 60947-1 & -2, UL 489, CSA C22.2 No. 5, CE marked, RoHS compliant.
Electrical Endurance Up to 8,000 operations at rated current.
Mechanical Endurance Up to 20,000 operations.
Operating Ambient Temperature -25°C to +70°C (Derating may apply above 40°C or 50°C, refer to manual).
Storage Temperature -50°C to +85°C
Protection Rating IP20 (for installation inside an enclosure)
Typical Applications Main distribution feeder protection, generator output protection, protection of industrial loads (motors, heaters), and as a main disconnect switch with overload protection in commercial switchboards.