The Schneider OSMC32N4C32 4P32A motor protection circuit breaker is an efficient and reliable solution for safeguarding motors and electrical circuits, providing robust protection for both industrial and commercial applications.
Type: Motor Protection Circuit Breaker (MPCB)
Rated Current (In): 32A
Poles: 4P (Four-Phase: Three-Phase + Neutral)
Voltage Rating:
Nominal Voltage: 400V AC (Three-Phase)
Rated Voltage Range: 380-415V AC
Breaking Capacity (Icu):
Icu (Ultimate Breaking Capacity): 10 kA (at 400V AC)
Protection Features:
Overload Protection:
Thermal overload protection with adjustable settings (overload protection range 0.7 to 1.1 times the rated current)
Short-circuit Protection:
Magnetic short-circuit protection with fixed settings to protect the circuit in case of a short-circuit fault
Phase Loss Protection:
Protects against phase loss or phase imbalance, which could damage the motor
Earth Fault Protection:
Optional earth leakage protection for additional safety
Motor Protection:
Specifically designed to protect motors from damage caused by electrical faults such as overloads and short circuits
Adjustable Trip Settings:
Adjustable overload settings for different motor protection needs
Certifications:
IEC 60947-2 compliant
UL 489 certified
CE certified
Auxiliary Features:
Optional auxiliary contacts for monitoring operational status
Optional undervoltage release and shunt trip for remote control and safety disconnection
Mounting:
DIN Rail Mounted for easy installation in industrial and commercial panels
Dimensions (HxWxD): Typically 170 x 120 x 140 mm (dimensions may vary slightly depending on model configuration)
Applications:
Motor Protection: Ideal for protecting motors in industrial and commercial environments, especially for motors rated up to 32A
Suitable for installation in motor control centers (MCC), distribution boards, and electrical control panels
Designed for use in systems where protection against overloads, short circuits, and phase loss is necessary to ensure motor longevity and safety