The Schneider Electric iID is a 4-Pole, 100A, 300mA Sensitivity Residual Current Circuit Breaker (RCCB) from the Acti 9 series. Designed for enhanced electrical fire protection and protection against indirect contact, it detects and interrupts earth leakage currents in three-phase systems with neutral.
Parameter Specification
Product Line / Range Acti 9 iID
Poles / Configuration 4-Pole (4P) - 3 Phases + Neutral
Rated Current (In) 100 A
Residual Current Sensitivity (IΔn) 300 mA
Residual Current Type Typically Type A (AC and pulsating DC) or Type AC (AC only). Must be specified.
Tripping Time Instantaneous or Selective (S-type with time delay). Must be specified.
Rated Voltage (Un) 230/400V AC
Rated Short-Circuit Capacity (Icn) Typically 6 kA or 10 kA (IEC/EN 61008-1)
Mechanical Durability Up to 20,000 operations
Electrical Durability Up to 4,000 operations at In
Connection Screw terminals for rigid and flexible conductors.
Mounting DIN Rail (35mm)
Standards IEC/EN 61008-1, CE certified
Operating Temperature -25°C to +60°C
Control & Indication Toggle handle with ON/OFF positions. Visual trip indicator.