ABL8 RPM24200
The Schneider Electric ABL8 RPM24200 is a programmable digital power meter from the PowerLogic PM800 series. This compact, DIN-rail mounted device is designed for accurate measurement, monitoring, and basic power quality analysis of single-phase or three-phase electrical systems.
DESCRIBE
Parameter Specification
Product Series / Range PowerLogic PM800 Series (Common market name) / ABL8RPM (Schneider internal code)
Model PM820 / PM822 or equivalent (RPM24200 is a specific variant)
*Note: "24200" typically indicates 3-phase 4-wire (3P4W) system, 200A direct input.*
Measurement Type 3-Phase, 4-Wire (3P4W) system
Rated Input Current (In) 200 A Direct Input (Built-in current transformers, no external CTs needed up to this rating)
Rated Input Voltage (Un) 57.7/100V, 120/208V, 230/400V, 277/480V (programmable)
Measured Parameters Voltage (V), Current (I), Frequency (Hz), Active/Reactive/Apparent Power (kW/kvar/kVA), Power Factor (PF), Active/Reactive Energy (kWh/kvarh), Demand, THD-V, THD-I (depending on firmware)
Accuracy Class 0.5% (for active energy, per IEC 62053-22)
Display Backlit LCD display with multiple screen configurations
Communication Ports Typically includes:
• 1x RS-485 (Modbus RTU protocol)
• Optional second communication port (e.g., Ethernet, Profibus) as per model variant.
Digital Inputs/Outputs Programmable Digital Inputs (DIs): Typically 2, for status monitoring (e.g., relay, pulse).
Programmable Relay Outputs (DOs): Typically 2, for alarm or control functions.
Pulse Output Energy pulse output (kWh, kvarh) via a dedicated terminal or programmable relay.
Power Supply Auxiliary Supply (Vs): Wide range, e.g., 85-265V AC/DC or 24V DC (depends on variant).
Mounting DIN Rail Mount (35mm)
Standards & Certifications IEC 61557-12, IEC 62053-21/22, UL, CE, MID (for energy measurement)
Operating Temperature -25°C to +70°C