The Schneider Electric Acti9 iC65 ELE 3P 40A 30mA is a three-pole, 40A, C-curve miniature circuit breaker with integrated Type E residual current protection (30 mA). This integrated device combines overcurrent/short-circuit protection and earth leakage protection in a single module.
Parameters:
Parameter Value / Description
Product Series Acti9 iC65
Rated Current (In) 40 A
Tripping Curve C Curve (5-10 x In). Suitable for circuits with moderate inrush currents.
Number of Poles 3P (For three-phase circuits, typically no neutral connection on the device).
Rated Residual Operating Current (IΔn) 30 mA
Residual Current Type Type E (Selective). This is an advanced type that provides protection against:
• AC residual currents.
• Pulsating DC residual currents (Type A).
• Smooth DC residual currents (a key differentiator from Type A).
Rated Voltage (Un) 400V AC (Three-phase)
Rated Breaking Capacity (Icn) 6 kA at 230/400V AC (IEC 60898-1)
Mechanical & Electrical Life ≥ 20,000 operations
Standards IEC/EN 61009-1 (RCBO standard)
Mounting Fixed on 35mm symmetrical DIN rail (EN 60715)
Width 54 mm (3 DIN modules)
Terminals Front cable entry, screw clamp terminals suitable for rigid and flexible conductors.
Trip Indication Visual indicator distinguishes between Overload/Short-Circuit trip and Residual Current trip.