The Schneider Electric Acti 9 iEZ EZD100E 4P 60A is a four-pole, 60A electronic circuit breaker from the advanced Acti 9 iEZ range. It is equipped with a basic E-type electronic trip unit. Designed for commercial and light industrial four-wire distribution systems, this device provides reliable and adjustable protection against overloads and short-circuits.
Parameters:
Parameter Value / Description
Frame Size (Iu) 100 A
Rated Current (In) 60 A (The long-time protection setting Ir is adjustable, typically within 0.4 - 1.0 x In).
Number of Poles 4 (L1, L2, L3, N)
Tripping Unit Type Electronic (E-type) – Basic adjustable protection unit.
Rated Operational Voltage (Ue) 400 V AC (3P+N)
Rated Insulation Voltage (Ui) 690 V
Rated Impulse Withstand Voltage (Uimp) 8 kV
Rated Ultimate Breaking Capacity (Icu) Typically 36 kA at 400V AC (IEC 60947-2).
Rated Service Breaking Capacity (Ics) 100% of Icu (IEC 60947-2, Category B).
Protection Functions L - Long-time delay (Adjustable Ir, tr), S - Short-time delay (Adjustable Isd, tsd), I - Instantaneous (Adjustable Ii). Ground fault (G) protection is NOT included in the base E unit (requires an optional iVigi module).
Standard IEC 60947-2
Mounting Fixed mounting on a dedicated base (included).
Connection Front connection with screw-clamp terminals.
Width 144 mm (4 DIN modules)
Neutral Pole Configuration Usually configured as 4P4D (4 Poles, 4 Protected Poles), meaning the neutral pole is fully protected like the phase poles. Other configurations (e.g., 4P3D) may be available.