The Schneider Electric TeSys GV2P-PM05C is a three-phase manual motor starter and protector (MMSP) from the GV2P series, an enhanced variant of the classic GV2 line. It is a compact, integrated device that combines a manual isolator switch, a thermal overload relay, and a magnetic short-circuit protector in a single unit.
Parameters:
Parameter Value / Description
Product Series / Frame Size TeSys GV2P, Size 05
Current Setting Range (Ir) 0.25 - 5.0 A (Continuously adjustable via a rotary dial to precisely match the motor's nameplate Full Load Current).
Short-Circuit Protection Magnetic trip, C Curve (Instantaneous trip range: 7 to 10 x Ir).
Rated Operational Voltage (Ue) Up to 690 V AC
Rated Insulation Voltage (Ui) 690 V
Rated Ultimate Breaking Capacity (Icu) 50 kA at 415V AC (IEC/EN 60947-2)
Number of Poles 3 (For the main motor power circuit)
Control Function Manual ON/OFF operation via an integrated rocker/toggle handle.
Trip Indication: Clear visual trip indicator (red flag) upon thermal overload.
Manual Reset: Required after a thermal trip (push-button reset).
Auxiliary Contacts Built-in 1 NO (97-98) + 1 NC (95-96) auxiliary contact block for signaling to control circuits.
Protection Functions Overload (Class 10): Bi-metal thermal relay with ambient temperature compensation.
Short-Circuit: Magnetic trip.
Phase Loss/Imbalance: Detected by the thermal relay.
Standards IEC/EN 60947-2 (Circuit Breaker), IEC/EN 60947-4-1 (Motor Starter)
Mounting Mounts on a 35mm symmetrical DIN rail (EN 60715).
Electrical Durability High mechanical endurance (typically ≥ 100,000 mechanical cycles).