The Schneider Electric ICNV 2P 50A is a self‑resetting over‑ and under‑voltage protection device designed for single‑phase AC circuits. It continuously monitors the supply voltage and automatically disconnects the load when the voltage goes outside pre‑defined safe limits to protect connected electrical equipment from damage due to over‑voltage or under‑voltage conditions.
Specifications
Product Type: Self‑reset over‑ and under‑voltage protective device
Series / Family: Acti9 iCNV
Model / Code: ICNV 2P 50A
Number of Poles: 2 (phase + neutral)
Mounting: DIN‑rail mountable
Application: Voltage protection for single‑phase AC circuits
Electrical Ratings
Rated Operational Voltage (Ue): 230 V AC at 50 Hz (between phase and neutral)
Supply Voltage Range: 50 V to 440 V AC (single‑phase)
Rated Current (Ie): 50 A continuous
Rated Insulation Voltage (Ui): 500 V
Rated Impulse Withstand Voltage (Uimp): 4 kV (between phases and phase to neutral)
Leakage Current: < 2 mA
Voltage Protection
Over‑Voltage Trip Thresholds & Delay:
~275 V — trip delay ~3–15 s
~300 V — trip delay ~1–5 s
~350 V — trip delay ~0.25–0.75 s
~400 V — trip delay ~0.1–0.2 s
Under‑Voltage Trip Range: ~50 V–160 V (trip delay ~0.6–5 s)
Auto‑Reset Delay: ~25–35 s after voltage returns to normal
Reset Points (example): ~253 V for over‑voltage reset; ~195 V for under‑voltage reset
Indicators & Operation
Status Indicators:
Green steady: normal operation
Green flashing: lock condition
Red steady: operating (tripped)
Response Time: < 1 s contact open; < 3 s contact close
Mechanical & Environmental
Clearance & Creepage: ~1.2 mm clearance, ~5.6 mm creepage
Installation: DIN‑rail (35 mm) with clip fastening
Terminal Connections: Bottom entry conductors
Installation Orientation: Vertical or horizontal in distribution board
Indoor Use: Designed for typical electrical distribution environments
Compact Dimensions: Width approx. 36 mm, height approx. 85 mm