The Schneider Electric WATSG250/4AVG is a dual-power automatic transfer switch (ATS) designed for use in three-phase electrical systems. This model is designed to manage load transfer between two independent power sources (typically from main power to a backup generator) for uninterrupted power supply to critical systems.
Specifications
General
Product Type: Automatic Transfer Switch (ATS)
Model: WATSG250/4AVG
Configuration: 4P (three-phase + neutral)
Rated Current: 250A
Mounting: Fixed installation in distribution panels or control cabinets
Application: Ensures continuous power supply by switching between primary and backup sources
Electrical Ratings
Rated Operational Voltage (Ue): Typically 400V AC, 50/60Hz (three-phase)
Rated Insulation Voltage (Ui): 690V AC
Rated Impulse Withstand Voltage (Uimp): 8kV
Short-Circuit Withstand Capacity: 25kA (breaking capacity)
Operating Frequency: 50/60Hz
Performance & Features
Automatic Switching: Automatically detects and switches to the backup power source in the event of a failure
Manual Override: Provides manual control to select the power source when required
Status Indicators: Visual indicators for clear identification of the current active power source
Remote Monitoring and Control: Option for integration with remote monitoring and control systems for greater flexibility
Mechanical & Environmental
Housing: Modular design for easy integration into control panels and distribution boards
Degree of Protection: IP40 (front face)
Operating Temperature Range: Typically -5°C to +40°C
Cable Connections: Screw terminals for secure and reliable connection of conductors
Mounting: Compatible with DIN rail or panel installation