The Schneider Electric iPRU 40R4P is a Residual Current Monitoring Unit (RCMU) from the Acti9 range. It is a non-tripping, monitoring-only device designed for continuous measurement and pre-alert signaling of earth leakage currents in electrical installations.
Specifications
Parameter Specification
Product Range Acti9 iPRU
Device Type Residual Current Monitoring Unit (RCMU) / Insulation Monitor
Model iPRU 40R4P
Number of Poles (Monitoring) 4 Poles (For 3-phase + Neutral systems)
Rated Residual Operating Current (IΔn) 40 mA (Main alarm threshold, typically factory-set)
Residual Current Type Detection Type A (Detects both AC and pulsating DC residual currents).
Adjustable Alarm Thresholds Yes. Typically includes:
• Pre-Alarm (PA): Adjustable (e.g., 20mA or 50% of IΔn).
• Main Alarm (MA): Fixed or adjustable at 40mA (100% IΔn).
Power Supply (Auxiliary Voltage) 24-240V AC/DC (Wide range, specific to this model variant).
Consumption Typically < 5VA.
Measurement Range 1 to 40mA (continuous monitoring).
Accuracy Typically ±5% of measured value.
Output Contacts 2 Changeover (CO) Relay Contacts (SPDT):
• 1 for Pre-Alarm (PA).
• 1 for Main Alarm (MA).
Contact Rating Typically 250V AC, 5A resistive.
Visual Indicators (LEDs) Power (Green), Pre-Alarm (Yellow), Main Alarm (Red).
Required External Sensor Must be used with a dedicated Toroidal Current Transformer (CT). Example: Schneider CSE200N series (size selected based on cable/busbar diameter).
Wiring to CT Via a standardized 4-pin connector or terminal block.
Mounting DIN Rail Mounting (EN 60715). Width: 4 Modules (72mm).
Standards Compliance IEC/EN 62020 (Electrical accessories - Residual current monitors for household and similar uses), IEC/EN 60947-1.
Ambient Temperature -25°C to +60°C (operational).
Pollution Degree PD2