Schneider Electric PM5500 is a multifunction panel‑mount power and energy meter from the PowerLogic™ PM5000 series, designed for advanced electrical measurement and monitoring in three‑phase distribution systems. It provides True RMS measurement of electrical parameters including voltage, current, power, energy, frequency, power factor, and power quality metrics with high accuracy. The PM5500 supports bidirectional energy metering, demand values with time stamps, harmonic and unbalance analysis, and configurable communications for integration into building automation and energy management systems. The meter’s graphical LCD display provides clear visualization of measured values and historical statistics, making it ideal for industrial, commercial, and utility‑grade metering applications.
Parameters
Brand: Schneider Electric
Series: PowerLogic PM5500 (PM5000 family)
Model / Part: PM5500 Power & Energy Meter
Product Type: Multifunction digital power and energy meter
Application: Energy, power, and power quality monitoring for three‑phase electrical systems
Display: Monochrome graphical LCD with white LED backlight, 128 × 128 resolution
Display Protection: Front IP54 (upgradeable to IP65 with accessory), body IP30
Mounting: Panel mount (vertical orientation)
Measurement Method: True RMS up to the 63rd harmonic, 128 samples per cycle
Voltage Input Range: 20 – 400 V L‑N / 20 – 690 V L‑L (Wye) or 20 – 600 V L‑L (Delta)
Measurement Category: CAT III
Current Input: CT secondary 5 A (Class 0.2S) or 1 A (Class 0.5S), 50 mA – 10 A range
Measured Parameters:
Voltage, Current (per phase and neutral)
Active, Reactive, Apparent Power
Power Factor, Frequency
Active, Reactive, Apparent Energy (four‑quadrant)
Min/Max, Demand, Peak values with timestamp
Harmonic / THD analysis, Unbalance values
Energy Accuracy: Active energy Class 0.2S; Reactive energy Class 2; Apparent energy Class 0.5
Power Accuracy: Active power Class 0.2; Reactive power Class 1; Apparent power Class 0.5
Voltage Accuracy: Class 0.1; Current accuracy Class 0.2
Frequency Accuracy: Class 0.05
Communication Interfaces:
RS‑485 (Modbus RTU / ASCII)
Ethernet (Modbus TCP, BACnet/IP, EtherNet/IP, DNP3*; model and firmware dependent)
Digital Inputs / Outputs: Configurable digital inputs and solid‑state digital outputs (model dependent)
Operating Frequency: 45 – 70 Hz
Operating Temperature Range: Typically –25 °C to +70 °C
Humidity: 5 % – 95 % RH non‑condensing
Pulse / Output Constants: Configurable metering pulses for kWh / kVAh / kVARh
Standards Compliance: IEC 61557‑12, IEC 61010‑1, IEC 61326‑1, and measurement category standards
Weight: Approx. 300–450 g (varies by model/configuration)